LSZH and Fire-Resistant power cable, for emergency circuits.
TOXFREE Plus 331 ZH RZ1-K AS+ is a fire-resistant cable, specially designed to ensure the power supply to emergency circuits in the event of fire. During a fire you need critical circuits to work for life safety (signaling lights, fume extractors, acoustic alarms, water pumps, etc) and a secure plant shutdown. For this reason, its use is highly recommended in public places such as: hospitals, tunnels, offices, production plants, laboratories, hotels, etc.
Technology
Conductor
- Electrolytic copper, class 5 (flexible), based on EN 60228 and IEC 60228.
Insulation
- Mica tape + XLPE
- The standard identification of insulated conductors is the following:
- 1 x Natural
- 2x Blue + Brown
- 3 G Blue + Brown + Yellow/green
- 4 G Brown + Black + Grey + Yellow/green
- 5 G Brown + Black + Grey + Yellow/green + Blue
Outer sheath
Low Smoke Zero Halogen (LSZH) polyolefin. Orange colour, non-toxic, fire retardant and fire resistant.
NOTES
- Low Voltage 0.6/1kV
- Maximum service temperature: 90ºC
- Industrial use / Public places / Emergency circuits
- Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1.
- UNE-EN 60332-1 / UNE-EN 60332-3 / UNE-EN 50267-1 / UNE-EN 50267-2 / UNE-EN 61034 / UNE-EN 50200 / UNE-EN 50363
CHEMICAL PERFORMANCE
Chemical & Oil resistance: Acceptable.
FIRE PERFORMANCE
- Fire non-propagation based on UNE-EN 60332-3 and IEC 60332-3.
- Fire resistant 180’ at 950ºC (cat C) category C,W & Z based on BS6387 (300/500V).
- Fire resistant: (PH120) mínimum 120 minutes at 840 ºC: Based on EN 50200 and IEC 60331-2 for Ø cable < 20 mm. Based on EN 50362 and IEC 60331-1 for Ø cable > 20 mm. 180’ at 950ºC (cat C) category C,W & Z based on BS6387.
- Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1.
- Low corrosive gases emission based on UNE-EN 60754-2 and IEC 60754-2.
- Low smoke emission based on UNE-EN 61034 and IEC 61034.: Light transmittance > 60%
- LSZH (Low Smoke Zero Halogen) based on UNE-EN 60754-1 and IEC 60754-1.
ELECTRICAL PERFORMANCE
Low Voltage 600/1000V
MECHANICAL PERFORMANCE
- Impact resistance: AG2 Medium severity.
- Minimum bending radius: x5 cable diameter.
THERMAL PERFORMANCE
- Maximum service temperature: 90ºC.
- Maximum short-circuit temperature: 250ºC (max. 5 s).
- Minimum service temperature: -40ºC (fixed and protected installations)
WATER PERFORMANCE
- Water Resistance: AD5 Jet
There is no datasheet available now.